GFPVT1500-10RS photovoltaic fuse (10x66) DC1500V

GFPVT1500-10RS photovoltaic fuse (10x66) DC1500V

GFPVT1500-10RS photovoltaic fuse (10x66) DC1500V

Lorem ipsum dolor sit amet, consectetur adipisicing elit. Libero velit id eaque ex quae laboriosam nulla optio doloribus! Perspiciatis, libero, neque, perferendis at nisi optio dolor!
Description
Lorem ipsum dolor sit amet, consectetur adipisicing elit. Libero velit id eaque ex quae laboriosam nulla optio doloribus! Perspiciatis, libero, neque, perferendis at nisi optio dolor!

Dimensions (mm)


Description
  • Low I²t value (low let-through energy)
  • Strong current limiting capability
  • Low voltage drop
  • Excellent DC performance

Standards & Approvals

  • Refer to UL-248-19 / IEC 60269-1/6
  • Reach declaration available upon request
  • RoHS compliant

Features & Benefits

  • The GFPVT1500-10RS solar fuse is designed to integrate into an in-line assembly within a wire harness
  • Provides photovoltaic (PV) protection meeting UL 248-19 for photovoltaic applications
  • Can be electrically insulated by either over-molding or using heat-shrink
  • Meets IEC 60269-6 electrical performance requirements

Product Characteristics

Item Test Condition/Methods Standard Performance
Time/Current 100% of current rating IEC 60269/UL248-19 No Fusing;4 hours Min.
113% of current rating  *IEC IEC 60269 60 Minutes Min.
145% of current rating  *IEC IEC 60269 60 Minutes Max.
105% of current rating *UL UL-248.19 60 Minutes Min.
135% of current rating *UL UL-248.19 60 Minutes Max.
200% of current rating IEC 60269/UL248-19;1-30A 4 Minutes Max.
IEC 60269/UL248-19;31-60A 6 Minutes Max.
Endurance Test 100% of rating current for 4 hours and testing Temperature rise at the last 5min. IEC 60269-6 UL248-19 ≤65K
  • Loading 100% Rated Current (1.0In A) for flowing, and it’s available to let current keep on flowing at least 4 hour without any melting.

Fuse Ratings

Part No. Fuse Amps Average @30KA/1500Vdc Power Loss (W) Approvals
A²s Melting A²s Clearing 80% 100% UL TUV
GFPVT1500-10A-10RS 10 342 890 2 3 ○ Pending ○ Pending
GFPVT1500-15A-10RS 15 550 1230 2.8 3.5 ○ Pending ○ Pending
GFPVT1500-20A-10RS 20 660 1450 3.2 5.5 ○ Pending ○ Pending
GFPVT1500-25A-10RS 25 885 1850 3.3 6 ○ Pending ○ Pending
GFPVT1500-30A-10RS 30 790 2750 3.8 6.8 ○ Pending ○ Pending
GFPVT1500-32A-10RS 32 1040 3550 4.2 8 ○ Pending ○ Pending
  • DC Cold Resistance are measured at <10% of rated current in ambient temperature of 25℃;