Features & Benefits
Partial Range Protection: Designed specifically for partial range protection needs.
Low I²t: Offers low I²t values and strong current limiting capability.
High Breaking Capacity: Ensures reliable operation under high fault conditions.
Industrial Applications: Suitable for industries like rail transit, electric vehicles, and boats.
Versatile Backup Protection: Provides backup protection after short-circuiting for energy storage systems, power systems, conductors, and other equipment.
[Annex: Download]
Volts: 1000Vdc
Amps: 25A-250A
Interrupting Capacity:
Max: 1000Vdc 50kA (or less)
Min: ≥ 3.0 In
Time Constant: ≤ 2±1 ms
Class Type: aR
Dimensions (mm)
![]()
Description
Standards & Approvals
-
Refer to UL 248.1 / UL 248.13
-
IEC 60269.1 / IEC 60269.4
-
REACH Declaration Available Upon Request
-
RoHS Compliant
Fuse Ratings
Part No. |
Fuse Amps |
Breaking Capacity |
Average @50KA/1000Vdc |
Power Loss (W) |
Installation torque |
A²s Melting |
A²t Clearing |
100% |
GFEVT1000-25A-36 |
25 |
50kA |
21 |
105 |
8 |
11.0±1.0 N·m |
GFEVT1000-32A-36 |
32 |
50kA |
38 |
185 |
10 |
11.0±1.0 N·m |
GFEVT1000-40A-36 |
40 |
50kA |
68 |
325 |
12 |
11.0±1.0 N·m |
GFEVT1000-50A-36 |
50 |
50kA |
155 |
745 |
16 |
11.0±1.0 N·m |
GFEVT1000-63A-36 |
63 |
50kA |
305 |
1450 |
20 |
11.0±1.0 N·m |
GFEVT1000-80A-36 |
80 |
50kA |
560 |
2480 |
22 |
11.0±1.0 N·m |
GFEVT1000-100A-36 |
100 |
50kA |
960 |
4820 |
25 |
11.0±1.0 N·m |
GFEVT1000-125A-36 |
125 |
50kA |
1640 |
8950 |
27 |
11.0±1.0 N·m |
GFEVT1000-160A-36 |
160 |
50kA |
4100 |
18750 |
36 |
11.0±1.0 N·m |
GFEVT1000-200A-36 |
200 |
50kA |
9560 |
39700 |
39 |
11.0±1.0 N·m |
GFEVT1000-225A-36 |
225 |
50kA |
11780 |
54700 |
42 |
11.0±1.0 N·m |
GFEVT1000-250A-36 |
250 |
50kA |
14500 |
70590 |
45 |
11.0±1.0 N·m |
*:If there are any requirements, please communicate with the original factory staff first. |
- DC Cold Resistance are measured at <10% of rated current in ambient temperature of 25℃;