Top

GFPVT1000 photovoltaic fuse (10X38) DC1000V

GFPVT1000 photovoltaic fuse (10X38) DC1000V

GFPVT1000 photovoltaic fuse (10X38) DC1000V

Lorem ipsum dolor sit amet, consectetur adipisicing elit. Libero velit id eaque ex quae laboriosam nulla optio doloribus! Perspiciatis, libero, neque, perferendis at nisi optio dolor!
Description
Lorem ipsum dolor sit amet, consectetur adipisicing elit. Libero velit id eaque ex quae laboriosam nulla optio doloribus! Perspiciatis, libero, neque, perferendis at nisi optio dolor!

Dimensions (mm)

Ferrule xxA-10R Dimensions

Axial bolt-on xxAP-10R Dimensions

Description



  • Low I²t value (low let-through energy)
  • Low voltage drop
  • Excellent DC performance
  • Variety of mounting options for flexibility

Standards & Approvals

  • Refer to UL-248-19 / IEC 60269-1/6
  • Reach declaration available upon request
  • RoHS compliant

Features & Benefits

  • The GFPVT1000 solar fuse is designed to integrate into an in-line assembly within a wire harness
  • Provides photovoltaic (PV) protection meeting UL 248-19 for photovoltaic applications
  • Can be electrically insulated by either over-molding or using heat-shrink
  • Meets IEC 60269-6 electrical performance requirements

Product Characteristics

Item Test condition/Methods Standard Performance
Time/Current 100% of current rating IEC 60269/UL248-19 No Fusing;4 hours Min.
113% of current rating *IEC IEC 60269 60 Minutes Min.
145% of current rating *IEC IEC 60269 60 Minutes Max.
105% of current rating *UL UL-248.19 60 Minutes Min.
135% of current rating *UL UL-248.19 60 Minutes Max.
200% of current rating IEC 60269/UL248-19;1-30A 4 Minutes Max.
IEC 60269/UL248-19;31-60A 6 Minutes Max.
Endurance Test 100% of rating current for 4 hours and testing Temperature rise at the last 5min. IEC 60269-6 UL248-19 ≤65K
  • Loading 100% Rated Current (1.0In A) for flowing, and it’s available to let current keep on flowing at least 4 hour without any melting.

Fuse Ratings


  • Ferrule xxA-10R


Part No. Fuse Amps Average @30KA/1000Vdc Power Loss (W) Approvals
A²s Melting A²s Clearing 80% 100% TUV
GFPVT1000-10A-10R 10 210 1175 1.1 1.5
GFPVT1000-12A-10R 12 252 1405 1.3 1.7
GFPVT1000-15A-10R 15 315 1757 1.6 2.3
GFPVT1000-16A-10R 16 326 1780 1.6 2.3
GFPVT1000-20A-10R 20 420 2340 2.1 2.9
GFPVT1000-25A-10R 25 525 2929 2.7 3.5
GFPVT1000-30A-10R 30 630 3515 3.2 4.2
GFPVT1000-32A-10R 32 890 3995 4 5.3
GFPVT1000-35A-10R 35 975 4545 4.6 6.2

Axial bolt-on xxAP-10R

Part No. Fuse Amps Average @30KA/1000Vdc Power Loss (W) Approvals
A²s Melting A²s Clearing 80% 100% TUV
GFPVT1000-10AP-10R 10 210 1175 1.1 1.5
GFPVT1000-12AP-10R 12 252 1405 1.3 1.7
GFPVT1000-15AP-10R 15 315 1757 1.6 2.3
GFPVT1000-16AP-10R 16 326 1780 1.6 2.3
GFPVT1000-20AP-10R 20 420 2340 2.1 2.9
GFPVT1000-25AP-10R 25 525 2929 2.7 3.5
GFPVT1000-30AP-10R 30 630 3515 3.2 4.2
GFPVT1000-32AP-10R 32 890 3995 4 5.3
GFPVT1000-35AP-10R 35 975 4545 4.6 6.2
  • DC Cold Resistance are measured at <10% of rated current in ambient temperature of 25℃